Hitachi SJ100 User Manual

Page 87

Advertising
background image

SJ100 Inverter

Conf

igur

ing

Dr
iv

e P

a

ra

m

e

ters

3–15

The following table shows the methods of torque control selection.

“A” Function

Run

Mode

Edit

Defaults

Func.

Code

Name /

SRW Display

Description

–FE

(CE)

–FU

(UL)

–FR

(Jpn)

Units

A_41 Torque boost method

selection

Two options:
00... Manual torque boost
01... Automatic torque boost

00

00

00

V-Boost Mode 0

A241 Torque boost method

selection, 2nd motor

Two options (for 2nd motor):
00... Manual torque boost
01... Automatic torque boost

00

00

00

2V-Boost Mode 0

A_42 Manual torque boost

value

Can boost starting torque
between 0 and 99% above
normal V/f curve, from 0 to
1/2 base frequency

11

11

11

V-Boost code 11

A242 Manual torque boost

value, 2nd motor

Can boost starting torque
between 0 and 99% above
normal V/f curve, from 0 to
1/2 base frequency

11

11

11

2V-Boost code 11

A_43 Manual torque boost

frequency adjustment

Sets the frequency of the V/f
breakpoint A in graph (top of
previous page) for torque boost

10.0

10.0

10.0

%

V-Boost F 10.0%

A243 Manual torque boost

frequency adjustment,
2nd motor

Sets the frequency of the V/f
breakpoint A in graph (top of
previous page) for torque boost

10.0

10.0

10.0

%

2V-Boost F 10.0%

A_44 V/f characteristic curve

selection

Two available V/f curves;
three select codes:
00... Constant torque
01... Reduced torque
02... Sensorless vector control

02

02

02

CONTROL SLV

A244 V/f characteristic curve

selection, 2nd motor

Two available V/f curves;
three select codes:
00... Constant torque
01... Reduced torque
02... Sensorless vector control

02

02

02

2CONTROL SLV

A_45 V/f gain setting

Sets voltage gain of the
inverter from 50 to 100%

100

100

100

%

V-Gain 100%

Advertising