SJ100 Inverter

Motor Control

Acce

ssor

ie

s

5–11

400V Class Inverters –The following tables
specify the braking options for 400V class
SJ100 inverters and the braking torque for
each option. You can connect a single braking
unit to the inverter, or two braking units for
additional braking torque.

Use one BRD–E2 braking unit for the braking torque listed in the following table.

Connect a second braking unit in parallel for additional braking torque listed in the
following table.

Inverter

+

Braking

unit

Braking

unit

SJ100 Inverter 400V Models

Braking Torque with BRD–EZ2 Braking Unit

Model Number

HP

Braking torque

without

braking unit

Using built-in

resistor only

External resistor added

HRB1

HRB2

HRB3

A

B

A

B

A

B

A

B

004HFE/HFU

1/2

50%

150%

120%

007HFE/HFU

1

50%

100%

80%

150%

120%

015HFE/HFU

2

50%

60%

60%

100%

80%

120%

100%

150%

120%

022HFE/HFU

3

20%

50%

50%

100%

80%

120%

100%

150%

120%

030HFE

4

20%

40%

40%

80%

60%

100%

80%

150%

120%

040HFE/HFU

5

20%

40%

40%

60%

60%

80%

60%

150%

120%

055HFE/HFU

7.5

20%

30%

30%

50%

50%

80%

60%

100%

80%

075HFE/HFU

10

20%

20%

20%

40%

40%

60%

40%

80%

80%

SJ100 Inverter 400V Models

Braking Torque with TWO (2) BRD–EZ2 Braking Units

Model Number

HP

Braking torque

without

braking unit

Using built-in

resistor only

External resistor added

HRB1

HRB2

HRB3

A

B

A

B

A

B

A

B

004HFE/HFU

1/2

50%

150%

120%

007HFE/HFU

1

50%

150%

120%

015HFE/HFU

2

50%

100%

80%

022HFE/HFU

3

20%

70%

70%

150%

120%

030HFE

4

20%

50%

50%

110%

90%

040HFE/HFU

5

20%

50%

50%

110%

90%

055HFE/HFU

7.5

20%

30%

30%

80%

80%

90%

90%

100%

100%

075HFE/HFU

10

20%

30%

30%

60%

60%

80%

80%

100%

100%