Dynamic Braking Usage Ratio

The inverter controls braking via a duty cycle
method (percent of the time braking is ON
versus total time). Parameter B_90 sets the
dynamic braking usage ratio. In the graph to
the right, the example shows three uses of
dynamic braking in a 100-second period. The
inverter calculates the average percentage
usage in that time (T%). The percentage of
usage is proportional to the heat dissipated. If
T% is greater than the B_90 parameter setting,
the inverter enters the Trip Mode and turns OFF the frequency output.

Please note the following:

• When B_90 is set for 0%, dynamic braking is not performed.

• When the T% value exceeds the limit set by B_90, dynamic braking ends.

• When mounting an external dynamic braking unit, set the usage ratio (B_90) to 0.0

and remove the external resistors.

• The cable from the external resistor to the inverter must not exceed 5 m (16 ft.) length.

• The individual wires from the resistor to the inverter must not be bundled together.

BRD

T%

t1 t2 t3

+

+

(

)

100 seconds

-------------------------------

100

×

=

B 90

ON

OFF

t1

t2

t3

t