DC Braking Settings

The DC braking feature can provide
additional stopping torque when
compared to a normal deceleration to a
stop. DC braking is particularly useful
at low speeds when normal decelera-
tion torque is minimal. When you
enable DC braking, the inverter injects
a DC voltage into the motor windings
during deceleration below a frequency you can specify (A_52). The braking power
(A_54) and duration (A_55) can both be set. You can optionally specify a wait time
before DC braking (A_53), during which the motor will free run (coast).

CAUTION: Be careful to avoid specifying a braking time that is long enough to cause
motor overheating. If you use DC braking, we recommend using a motor with a built-in
thermistor, and wiring it to the inverter’s thermistor input (see

“Thermistor Thermal

Protection” on page 4–22

). Also refer to the motor manufacturer’s specifications for

duty-cycle recommendations during DC braking.

DC braking

Free run

Running

A 53

A 55

t

0

+

–

“A” Function

Run

Mode

Edit

Defaults

Func.

Code

Name /

SRW Display

Description

–FE

(CE)

–FU

(UL)

–FR

(Jpn)

Units

A_51 DC braking enable

Two options; select codes:
00... Disable
01... Enable

✘

00

00

00

—

DCB SW OFF

A_52 DC braking frequency

setting

The frequency at which DC
braking occurs,
range is 0.5 to 10 Hz

✘

0.5

0.5

0.5

Hz

DCB F 00.5Hz

A_53 DC braking wait time

The delay from the end of Run
command to start of DC
braking (motor free runs until
DC braking begins)

✘

0.0

0.0

0.0

sec.

DCB WAIT 0.0s

A_54 DC braking during

deceleration

Applied level of DC braking
force, settable from 0 to 100%

✘

0

0

0

%

DCB V 000

A_55 DC braking time for

deceleration

Sets the duration for DC
braking, range is 0.1 to 60.0
seconds

✘

0.0

0.0

0.0

sec.

DCB T 00.0s