Output deviation for pid control – Hitachi SJ100 User Manual

Page 146

Advertising
background image

SJ100 Inverter

Oper

ations

and Monitor

ing

4–29

Output Deviation for PID Control

The PID loop error is defined as the
magnitude (absolute value) of the differ-
ence between the Setpoint (target value)
and the Process Variable (actual value).
When the error magnitude exceeds the
preset value for C_44, the [OD] terminal
signal turns ON. Refer to

“PID Loop

Operation” on page 4–39

.

NOTE: The example circuit in the table above drives a relay coil. Note the use of a diode
to prevent the negative-going turn-off spike generated by the coil from damaging the
inverter’s output transistor.

[OD]

Signal

SP, PV

C 44

C 44

1
0

t

ON

ON

Setpoint

Process variable

Option

Code

Terminal

Symbol

Function Name

Output

State

Description

04

OD

Output Deviation for
PID Control

ON

when PID error is more than the set threshold for
the deviation signal

OFF

when PID error is less than the set threshold for
the deviation signal

Valid for outputs:

11, 12, AL0 – AL2

Required settings:

C_44

Notes:

The default difference value is set to 3%. To change
this value, change parameter C_44 (deviation
level).

RY

+

12 11

L

H O OI

FM CM2

Example (requires output configuration—
see page

3–38

):

Inverter output
terminal circuit

See I/O specs on page

4–6

.

OD

Advertising