Monitoring Parameters with the Display

After using the keypad for parameter editing,
it’s a good idea to switch the inverter from
Program Mode to Monitor Mode and close
the panel door (puts the keys for parameter
editing out of sight). This will also turn out
the PRG LED, and the Hertz or Ampere LED
indicates the display units.

For the powerup test, monitor the motor speed indirectly by viewing the inverter’s output
frequency. The output frequency must not be confused with base frequency (50/60 Hz)
of the motor, or the carrier frequency (switching frequency of the inverter, in the kHz
range). The monitoring functions are in the “D” list, located near the top left of the

“Keypad Navigational Map” on page 2–23

.

Output frequency (speed) monitor - Resuming the keypad programming from the
previous table, follow the steps in the table below.

When the

d

01

function code appeared, the PRG LED went OFF. This confirms the

inverter is no longer in programming mode, even while you are selecting the particular
monitoring parameter. After pressing the Function key, the display shows the current
speed (is zero at this point).

Running the Motor

If you have programmed all the parameters up to this point, you’re ready to run the
motor! First, review this checklist:

1. Verify the Power LED is ON. If not, check the power connections.

2. Verify the Run Key Enable LED is ON. If not, review the programming steps to find

the problem.

3. Verify the PRG LED is OFF. If it is ON, review the instructions above.

4. Make sure the motor is disconnected from any mechanical load.

5. Turn the potentiometer to the MIN position (completely counterclockwise).

6. Now, press the RUN key on the keypad. The RUN LED will turn ON.

7. Slowly increase the potentiometer setting in clockwise fashion. The motor should

start turning when the indicator is in the 9:00 position and beyond.

8. Press the STOP key to stop the motor rotation.

Action

Display

Func./Parameter

Press the

key.

“H” Group selected

Press the

key.

Output frequency selected

Press the

key.

Output frequency displayed

Hz

POWER

A

RUN

PRG

RUN

STOP

RESET

MIN

MAX

HITACHI

5 0.0

FUNC.

H - -

1

d

0 1

FUNC.

0.0