Analog input settings – Hitachi SJ100 User Manual

Page 82

Advertising
background image

“A” Group: Standard Functions

Configur

ing

Dr

iv

e P

a

ra

m

e

ters

3–10

Analog Input Settings

The inverter has the capability to accept an external analog input that can command the
output frequency to the motor. Voltage input (0 –10V) and current input (4–20mA) are
available on separate terminals ([O] and [OI], respectively). Terminal [L] serves as
signal ground for the two analog inputs. The analog input settings adjust the curve
characteristics between the analog input and the frequency output.

In the graph below (left), A_13 and A_14 select the active portion of the input voltage or
current range. The parameters A_11 and A_12 select the start and end frequency of the
converted output frequency range, respectively. Together, these four parameters define a
line segment as shown (below, right). When the line does not begin at the origin, A_15
defines whether the inverter outputs 0Hz or the A_11 frequency when the analog input
value is less than the A_13 setting (determines the non-linear part of the translation).

A203 Base frequency setting,

2nd motor

Settable from 50 Hz to the
maximum frequency

50.0

60.0

60.0

Hz

2F-BASE 060Hz

A_04 Maximum frequency

setting

Settable from the base
frequency up to 360 Hz

50.0

60.0

60.0

Hz

F-MAX 060Hz

A204 Maximum frequency

setting, 2nd motor

Settable from the base
frequency up to 360 Hz

50.0

60.0

60.0

Hz

2F-MAX 060Hz

“A” Function

Run

Mode

Edit

Defaults

Func.

Code

Name /

SRW Display

Description

–FE

(CE)

–FU

(UL)

–FR

(Jpn)

Units

A 12

A 11

A 13

A 14

A 12

A 11

A_15 = 00

A_15 = 01

A 13

A 14

Frequency

Frequency

0V

4mA

10V

20mA

% Input scale

% Input scale

0V

4mA

10V

20mA

0

0

%

%

Advertising