Motor control accesso ri es – Hitachi SJ100 User Manual

Page 166

Advertising
background image

Dynamic Braking

Motor Control

Accesso

ri

es

5–8

Selecting Braking Resistors for Internal Braking Units

You can add one or more resistors to your inverter configuration to increase braking
torque performance. The tables below lists the resistor types for inverter models with
internal braking units. Tables for inverters with external braking units are on the next two
pages.

• Total Ohms – lists the resistance value of the resistor or, if using multiple resistors,

their combined resistance

• Total Watts – lists the power dissipation of the resistor or, if using multiple resistors,

their combined power dissipation

• Maximum Duty Cycle – the maximum allowable percentage of braking time over any

100-second interval to avoid overheating the resistor(s)

• Maximum Braking Torque – the maximum braking torque that the inverter / resistor

combination can deliver

The table below lists 200V-class inverter models
with built-in braking units. Depending on the
desired braking torque or on the inverter model,
the resistor selection specifies multiple resistors
in a parallel or series combination. The example
diagram shows a parallel configuration. Please
refer to the braking resistor documentation for
detailed wiring diagrams.

Inverter

JRB x (2) parallel

+

RB

200V Class

Dynamic Braking Resistor Selection

JRB Series

SRB/NSRB Series

HRB Series

SJ100

Model

Number

HP

Type &

(Qty)

Total

Ohms

Total

Watts

Max.

Duty

Cycle

(%)

Type &

(Qty)

Total

Ohms

Total

Watts

Max.

Duty

Cycle

(%)

Type &

(Qty)

Total

Ohms

Total

Watts

Max.

Duty

Cycle

(%)

002NFE/NFU

1/4

120–1

180

120

5.0

200–1

180

200

10.0

004NFE/NFU

1/2

120–1

180

120

5.0

200–1

180

200

10.0

005NFE

3/4

120–1

180

120

5.0

200–1

180

200

10.0

007NFE/NFU

1

120–2

100

120

2.5

200–2

100

200

7.5

011NFE

1.5

120–2

100

120

2.5

200–2

100

200

7.5

015NFE/NFU

2

120–3

50

120

1.5

300–1

50

300

7.5

022NFE/NFU

3

120–3

50

120

1.5

300–1

50

300

7.5

037LFU

5

120–4

35

120

1.0

400–1

35

400

7.5

055LFU

7.5

120–4

x (2) in
parallel

17.5

240

1.0

400–1

x (2) in
parallel

17.5

800

7.5

HRB3

17

1200

10.0

075LFU

10

17.5

240

1.0

17.5

800

7.5

HRB3

17

1200

10.0

Advertising