background image

“A” Group: Standard Functions

Configur

ing

Dr

iv

e P

a

ra

m

e

ters

3–18

Jump Frequencies – Some motors or machines exhibit resonances at particular
speed(s), which can be destructive for prolonged running at those speeds. The inverter
has up to three jump frequencies as shown in the graph. The hysteresis around the jump
frequencies causes the inverter output to skip around the sensitive frequency values.

Jump frequencies

A 63

A 64

Output

frequency

Frequency command

A 64

A 66
A 66

A 68
A 68

A 65

A 67

Hysteresis values

0

“A” Function

Run

Mode

Edit

Defaults

Func.

Code

Name /

SRW Display

Description

–FE

(CE)

–FU

(UL)

–FR

(Jpn)

Units

A_63,
A_65,

A_67

Jump (center)
frequency setting

Up to 3 output frequencies can
be defined for the output to
jump past to avoid motor
resonances (center frequency)
Range is 0.0 to 360.0 Hz

0.0
0.0
0.0

0.0
0.0
0.0

0.0
0.0
0.0

Hz

JUMP F1 000.0Hz
JUMP F2 000.0Hz
JUMP F3 000.0Hz

A_64,
A_66,

A_68

Jump (hysteresis)
frequency width setting

Defines the distance from the
center frequency at which the
jump around occurs
Range is 0.0 to 10.0 Hz

0.5
0.5
0.5

0.5
0.5
0.5

0.5
0.5
0.5

Hz

JUMP W1 00.50Hz
JUMP W2 00.50Hz
JUMP W3 00.50Hz

Advertising