Terminal Dimensions and Torque Specs

The terminal screw dimensions for all SJ100 inverters are listed in table below. This
information is useful in sizing spade lug or ring lug connectors for wire terminations.

CAUTION: Fasten the screws with the specified fastening torque in the table below.
Check for any loosening of screws. Otherwise, there is the danger of fire.

When connecting wiring, use the tightening torque listed in the following table to safely
attach wiring to the connectors.

Wire the Inverter Input to a Supply

Step 6: In this step, you will connect wiring to
the input of the inverter. First, you must deter-
mine whether the inverter model you have
requires three-phase power only, or if it can
accept either single-phase or three-phase power.
All models have the same power connector
terminals [L1], [L2], and [N/L3]. So, you must
refer to the specifications label (on the side of
the inverter) for the acceptable power source
types! For inverters that can accept single-
phase power and are connected that way,
terminal [L2] will remain unconnected.
The wiring example to the right shows an SJ100
inverter wired for 3-phase input. Note the use of
ring lug connectors for a secure connection.

Connector

Number

of Screw

Terminals

Models 002NF,

004NF, 005NF

Models 007NF-

022NF, 037LF,

004HF - 040HF

Models 055LF,

075LF, 055HF,

075HF

Screw

Diameter

Width

(mm)

Screw

Diameter

Width

(mm)

Screw

Diameter

Width

(mm)

Power Terminals

12

M3.5

7.1

M4

9

M5

13

Control Signal

16

M2

M2

M2

Alarm Signal

3

M3

M3

M3

Ground Terminals

2

M4

M4

M5

Screw

Tightening Torque

Screw

Tightening Torque

Screw

Tightening Torque

M2

0.2 N•m (max. 0.25 N•m) M3.5

0.8 N•m (max. 0.9 N•m)

M5

2.0 N•m (max. 2.2 N•m)

M3

0.5 N•m (max. 0.6 N•m)

M4

1.2 N•m (max. 1.3 N•m)

6