SJ100 Inverter

Oper

ations

and Monitor

ing

4–31

The alarm output terminals are connected as shown below (left) by default. The contact
logic can be inverted as shown (below right) by using the parameter setting C_33. The
relay contacts normally open (N.O.) and normally closed (N.O.) convention uses
“normal” to mean the inverter has power and is in Run or Stop Mode. The relay contacts
switch to the opposite position when it is in Trip Mode or when input power is OFF.

N.C. contacts (after initialization)

N.O. contact (inverted by C_33 setting)

During normal running

When an alarm occurs

or power is turned OFF

During normal running

or power is turned OFF

When an alarm occurs

AL0

AL2

AL1

AL0

AL2

AL1

AL0

AL2

AL1

AL0

AL2

AL1

Contact

Power

Run

State

AL0-

AL1

AL0-

AL2

N.C.

(after

initialize,

C_33=01)

ON

Normal

Closed

Open

ON

Trip

Open

Closed

OFF

Open

Closed

Contact

Power

Run

State

AL0-

AL1

AL0-

AL2

N.O.

(set

C_33=00)

ON

Normal

Open

Closed

ON

Trip

Closed

Open

OFF

Open

Closed