Analog and Digital Monitor Output

In the system design for inverter applications it is useful to monitor the inverter operation
from a remote location. In some cases, this requires only a panel-mounted analog meter
(moving-coil type). In other cases, a controller device such as a PLC may command the
inverter frequency and other functions. Sometimes it is useful to have the inverter
transmit the (real-time) output frequency value back to the controller to confirm actual
operation. The monitor output function [FM] serves these purposes.

The inverter provides an analog/digital output
primarily for frequency monitoring on terminal
[FM] (frequency monitor). It uses terminal [L] as
analog GND reference. You can configure
terminal [FM] to transmit the inverter current
output or frequency output in pulse-width
modulated
format (PWM). You can also config-
ure terminal [FM] to output the frequency value in a frequency-modulated (FM) format.

The following table lists terminal [FM] configurations. Use function C_23 to configure.

PWM Signal Type

The pulse-width modulated signal at terminal
[FM] is primarily designed for driving a moving-
coil meter. The PWM signal is automatically
averaged by the inertia of the moving-coil mecha-
nism—converting the PWM signal to an analog
representation. Be sure to use a 10V full-scale DC
voltmeter.

The signal characteristics of terminal [FM] in PWM configuration is shown below:

To calibrate the meter reading, generate a full-scale output (always ON) at terminal
[FM]. Then use parameter B_81(gain setting from 0 to 255) to adjust the corresponding
full-scale reading of the meter. For example, when the inverter output frequency is
60 Hz, change the value of B_81 so that the meter reads 60 Hz.

Func.

Code

Description

Waveform

Full Scale value

C_23

00

Output frequency

PWM

0 – Max. frequency (Hz)

01

Output current

PWM

0 – 200%

02

Output frequency

FM

0 – Max. frequency (Hz)

A GND

Analog/digital Output

12 11

L

H O OI

FM CM2

See I/O specs on page

4–6

.

0 to 10V,

1 mA

12 11

L

H O OI

FM CM2

+

Inverter output current

[FM]

Inverter output frequency

Pulse-width modulation (analog)

PWM scale factor

C_23 = 00

C_23 = 01

B 81

10V

0V

T

T = 4 ms

t

[FM] Output

t

T

---

=

t