General specifications, Getting star ted – Hitachi SJ100 User Manual

Page 28

Advertising
background image

SJ100 Inverter

Getting Star

ted

1–9

General Specifications

The following table applies to all SJ100 inverters.

Item

400V Class Specifications, continued

SJ100 inverters,
400V models

CE version

030HFE

040HFE

055HFE

075HFE

UL version

040HFU

055HFU

075HFU

Applicable motor size *2

kW

3.0

4.0

5.5

7.5

HP

4

5

7.5

10

Rated capacity (460V) kVA

6.2

6.6

10.3

12.7

Rated input voltage

3-phase: 380 to 460V ±10%, 50/60 Hz ±5%

Rated input current (A)

10.0

11.0

16.5

20.0

Rated output voltage *3

3-phase: 380 to 460V (corresponding to input voltage)

Rated output current (A)

7.8

8.6

13

16

Efficiency at 100% rated output (%)

95.4

96.2

96.0

96.5

Watt loss,
approximate (W)

at 70% output

100

108

156

186

at 100% output

138

151

219

261

Starting torque *6

180% or more

Dynamic braking
approx. %
torque, short time
stop *7

without resistor,
from 50/60 Hz

20%:

≤ 50Hz

20%:

≤ 60Hz

with resistor

100%

80%

DC braking

Variable operating frequency, time, and braking force

Weight

kg

2.8

2.8

5.5

5.7

lb

6.17

6.17

12.13

12.57

Item

General Specifications

Protective housing *1

IP20

Control method

Sine wave pulse-width modulation (PWM) control

Output frequency range *4

0.5 to 360 Hz

Frequency accuracy

Digital command: 0.01% of the maximum frequency
Analog command: 0.1% of the maximum frequency (25

°C ± 10°C)

Frequency setting resolution

Digital: 0.1 Hz; Analog: max. frequency/1000

Volt./Freq. characteristic *5

V/f optionally variable, V/f control (constant torque, reduced
torque), sensorless vector control

Overload current rating

150%, 60 seconds

Acceleration/deceleration time

0.1 to 3000 sec., (linear accel/decel), second accel/decel setting
available

Advertising