Using Intelligent Output Terminals

Oper

ations

and Monitor

ing

4–28

Overload Advance Notice Signal

When the output current exceeds a preset
value, the [OL] terminal signal turns ON.
The parameter C_41 sets the overload
threshold. The overload detection circuit
operates during powered motor opera-
tion and during regenerative braking. The
output circuits use open-collector
transistors, and are active low.

NOTE: The example circuit in the table above drives a relay coil. Note the use of a diode
to prevent the negative-going turn-off spike generated by the coil from damaging the
inverter’s output transistor.

[OL]

Signal

C 41

C 41

1
0

ON

t

ON

Current

threshold

regeneration

power running

threshold

Option

Code

Terminal

Symbol

Function Name

Output

State

Description

03

OL

Overload Advance
Notice Signal

ON

when output current is more than the set thresh-
old for the overload signal

OFF

when output current is less than the set threshold
for the overload signal

Valid for outputs:

11, 12, AL0 – AL2

Required settings:

C_41

Notes:

The default value is 100%. To change the level
from the default, set C_41 (overload level).

The accuracy of this function is the same as the
function of the output current monitor on the [FM]
terminal (see

“Analog and Digital Monitor Output”

on page 4–33

).

RY

+

12 11

L

H O OI

FM CM2

Example (requires output configuration—
see page

3–38

):

Inverter output
terminal circuit

See I/O specs on page

4–6

.

OL