Panel direction, Panel acceleration/deceleration select, Panel reset selection – Toshiba W7 User Manual

Page 101: Panel pid control, Panel operation inhibit selection, Overvoltage stall level (fast)

Advertising
background image

W7 ASD Installation and Operation Manual

95

Overvoltage Stall Level (fast)

Program

Protection Settings

Overvoltage Stall Level (fast)

This parameter sets the upper DC bus voltage threshold that, once exceeded,
will cause an Overvoltage Stall. An Overvoltage Stall increases the output
frequency of the ASD during deceleration for a specified time in an attempt to
prevent an Overvoltage Trip.

If the overvoltage condition persists for over 250 µ S, an Overvoltage Trip will
be incurred.

Note: This feature may increase deceleration times.

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 50.00

Maximum — 250.0

Units — %

Panel Acceleration/Deceleration Select

Program

Panel Control

Panel Acceleration/Deceleration Select

This parameter is used to select 1 of 4 accel/decel profiles that may be
configured and run. Each accel/decel profile is comprised of 3 user settings:
Acceleration, Deceleration, and Pattern.

Settings:

Acceleration/Deceleration #1

Acceleration/Deceleration #2

Acceleration/Deceleration #3

Acceleration/Deceleration #4

Parameter Type — Selection List

Factory Default — Acceleration/
Deceleration #1

Changeable During Run — Yes

Panel Direction

Program

Panel Control

Panel Direction

This parameter sets the motor direction while operating from the keypad.

Parameter Type — Selection List

Factory Default — Forward

Changeable During Run — Yes

Panel Operation Inhibit Selection

Program

Utilities

Display Attributes

Panel Operation Inhibit

Selection

This parameter disables the selected keypad function.

Settings:

Allow All Keys
Allow Emergency Off Only

Parameter Type — Selection List

Factory Default — Allow All Keys

Changeable During Run — Yes

Panel PID Control

Program

Panel Control

Panel PID Control

Enables/Disables PID control while operating from the keypad.

Parameter Type — Selection List

Factory Default — Enabled

Changeable During Run — Yes

Panel Reset Selection

Program

Panel Control

Panel Reset Selection

Enables/Disables the ability to reset the system from the keypad.

Parameter Type — Selection List

Factory Default — Enabled

Changeable During Run — Yes

Overvoltage Stall Level (fast)

Panel Reset Selection