Heading2 - i/o and control, I/o and control, I/o and control on pg. 17 – Toshiba W7 User Manual

Page 23

Advertising
background image

W7 ASD Installation and Operation Manual

17

Control Terminal Strip

I/O and Control

The W7 ASD can be controlled by several input types and combinations thereof, as well as operate
within a wide range of output frequency and voltage levels. This section describes the ASD control
methods and supported I/O functions.

The Control Terminal Strip PCBA (P/N 48570) supports discrete and analog I/O functions.

The Control Terminal Strip is shown in

Figure 5 on pg. 20

.

Table 2

and lists the names, the default

settings (where applicable), and the descriptions of the input and output terminals.

Figure 17 on pg. 24

shows the basic connection diagram for the W7 ASD system.

Table 2. Control Terminal Strip default assignment terminal names and functions.

Terminal

Name

Input/Output

Terminal Function

(default setting if programmable)

Circuit Config.

ST

Discrete Input

Standby (jumper to CC to operate the unit) — Multifunctional
programmable discrete input (see

Installation Notes on pg. 13

for further

information on this terminal).

Figure 7 on pg. 23.

RES

Discrete Input

Reset — Multifunctional programmable discrete input.

F

Discrete Input

Forward — Multifunctional programmable discrete input.

R

Discrete Input

Reverse — Multifunctional programmable discrete input.

S1

Discrete Input

Preset Speed 1 — Multifunctional programmable discrete input.

S2

Discrete Input

Preset Speed 2 — Multifunctional programmable discrete input.

S3

Discrete Input

Preset Speed 3 — Multifunctional programmable discrete input.

S4

Discrete Input

Emergency Off — Multifunctional programmable discrete input.

RR

Analog Input

RR — Multifunction programmable analog input

(0.0 to 10 volt input — 0 to 80 Hz output). Reference CC.

Figure 8 on pg. 23.

RX

Analog Input

RX — Multifunctional programmable analog input

(-10 to +10 VDC input — -80 to +80 Hz output). Reference CC.

Figure 9 on pg. 23.

II

Analog Input

II — Multifunctional programmable analog input (4 [0] to 20 mADC
input — 0 to 80 Hz output) (see

Figure 5 on pg. 20

for the location of the

II terminal). Reference CC.

Figure 10 on pg. 23.

VI

Analog Input

VI — Multifunctional programmable analog input

(0 to 10 VDC input — 0 to 80 Hz output). Reference CC.

P24

DC Output

24 VDC @ 50 mA output.

Figure 11 on pg. 23.

PP

DC Output

PP — 10.0 VDC voltage source for the external potentiometer.

Figure 12 on pg. 23.

OUT1

Discrete Output Low Frequency — Multifunctional programmable discrete output.

Figure 13 on pg. 23.

OUT2

Discrete Output Reach Frequency — Multifunctional programmable discrete output.

FP

Output

Frequency Pulse — an output pulse train that has a frequency which is
based on the output frequency of the ASD.

Figure 14 on pg. 23.

AM

Output

Produces an output current that is proportional to the magnitude of the
function assigned to this terminal (see

Table 8 on page 142

).

Figure 15 on pg. 23

FM

Output

FLC

Output

Fault relay (common).

Figure 16 on pg. 23.

FLB

Output

Fault relay (N.C.).

FLA

Output

Fault relay (N.O.).

CC

Control common (Do Not connect to Earth Gnd).

Discrete Input Terminals

On = connected to CC.

Analog Input terminals reference CC.

Advertising