Comm Error

• Communication malfunction.

• Improper or loose connection.

• Improper system settings.

Ctrl Undervolts

• This fault is caused by an undervoltage condition at the 5, 15, or the 24 VDC

supply.

• 3-phase input voltage low.

CPU Error

• CPU malfunction.

Main Undervolts

• 3-phase input voltage low.

• Defective control board.

• Excessive load on the power supply.

• Undervoltage/Ridethrough settings require adjustment.

Fuse

• Internal DC bus fuse is open.

DBR Overcurrent

• ASD inability to discharge the bus voltage during regeneration.

• No dynamic braking resistor (DBR) installed.

• Deceleration time is too short.

• Improper DBR setup information.

• Defective IGBT7 (or IGBT7 ckt.).

• 3-phase input voltage is above specification.

DBR Overload

• Deceleration time is too short.

• DBR setting adjustment required.

• Overvoltage Stall setting adjustment required.

GND Fault

• Ground fault at the motor.

• Ground fault at the output of the ASD.

• Current leakage to Earth Ground.

Ctrl EEPROM Err

• Internal EEPROM malfunction.

EEPROM Write Err

• EEPROM write malfunction.

E-Off

• Emergency Off command received via EOI or remotely.

Encoder Loss

• Encoder signal missing while running during closed-loop operation.

Flash Error

• Flash memory malfunction.

Gate Array Error

• Defective Gate Array or Gate Array malfunction.

In(put) Phase Loss

• 3-phase input to the ASD is low or missing.

Load Drooping

• Load requirement is in excess of the capabilities of the motor.

Load End OC

• Improper wiring at the ASD output to the motor.

Under Curr(ent) Trip

• Improper Low Current detection level setting.

Main EEPROM Err

• Internal EEPROM malfunction.

Note:

The event that caused the Trip(s) must be corrected or must decrease to less than the threshold