R terminal on pg. 111, For m, R terminal – Toshiba W7 User Manual

Page 117: Rs232/rs485 wire count, Rs232/rs485 response time, Rs232/rs485 master output

Advertising
background image

W7 ASD Installation and Operation Manual

111

RS232/RS485 Master Output

Program

Communication Settings

RS232/RS485 Master Output

In a master/follower configuration, this setting determines the output parameter
of the master ASD that will be used to control the applicable follower ASDs.

Note: Select Normal if TTL Master Out is configured as a Master

Output controller. Otherwise, a keypad failure will result.

Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.

Settings:

Normal (No Slave)
Frequency Reference
Output Command Frequency
Torque Command
Output Torque

Parameter Type — Selection List

Factory Default — Normal (No Slave)

Changeable During Run — Yes

RS232/RS485 Response Time

Program

Communication Settings

RS232/RS485 Response Time

This parameter sets the RS232/RS485 response delay time.

Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 2.00

Units — Seconds

RS232/RS485 Wire Count

Program

Communication Settings

RS232/RS485 Wire Count

This parameter sets the communications protocol to the 2 or 4 wire method.

Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.

Settings:

2 wire
4 wire

Parameter Type — Selection List

Factory Default — 4-Wire

Changeable During Run — Yes

R Terminal

Program

Terminal Settings

Input Terminals

R Terminal

Assignment

This parameter selects the functionality of the R discrete input terminal.

In addition, the input terminal must be specified as Normally Open or
Normally Closed.

This parameter sets the programmable R terminal to 1 of the 69 possible
functions that are listed in

Table 6 on page 138

.

Parameter Type — Selection List

Factory Default — Reverse

Changeable During Run — No

RS232/RS485 Master Output

R Terminal