91

OUT5 Terminal

Program

Terminal Settings

Output Terminals

OUT5 Terminal

Assignment

This parameter sets the functionality of the OUT5 output contacts to 1 of the 58
possible functions that are listed in

Table 7 on page 141

.

The on and off delay times of the OUT5 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.

In addition, the output contacts must be specified as Normally Open or
Normally Closed.

Parameter Type — Selection List

Factory Default — Upper Limit

Changeable During Run — No

OUT6 Off Delay

Program

Terminal Settings

Terminal Delays

Output Terminal

Delays

OUT6 Off Delay

Once the condition is met to change the state of the OUT6 output contacts, this
parameter delays the response of the contacts by the programmed value (see
waveforms at

FL Off Delay

).

The on and off delay times of the OUT6 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.

Parameter Type — Numerical

Factory Default — 2.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

OUT6 On Delay

Program

Terminal Settings

Terminal Delays

Output Terminal

Delays

OUT6 On Delay

This parameter delays the response of the OUT6 output contacts by the
programmed value (see waveforms at

FL On Delay

).

The delay may be increased to prevent relay chatter.

Parameter Type — Numerical

Factory Default — 2.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

OUT6 Terminal

Program

Terminal Settings

Output Terminals

OUT6 Terminal

Assignment

This parameter sets the functionality of the OUT6 output contacts to 1 of the 58
possible functions that are listed in

Table 7 on page 141

.

The on and off delay times of the OUT6 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.

In addition, the output contacts must be specified as Normally Open or
Normally Closed.

Parameter Type — Selection List

Factory Default — Reach Speed

Changeable During Run — No

OUT7 Off Delay

Program

Terminal Settings

Terminal Delays

Output Terminal

Delays

OUT7 Off Delay

Once the condition is met to change the state of the OUT7 output contacts, this
parameter delays the response of the contacts by the programmed value (see
waveforms at

FL Off Delay

).

The on and off delay times of the OUT7 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.

Parameter Type — Numerical

Factory Default — 2.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS