Power-line switching, Power-line switching frequency – Toshiba W7 User Manual

Page 105

Advertising
background image

W7 ASD Installation and Operation Manual

99

Power-Line Switching

Program

Special Control

Power-Line Switching Frequency

This parameter Enables/Disables the Powerline Switching feature. When
enabled, the system is instructed to discontinue using the output of the drive and
to switch to the commercial power in the event of a trip or when reaching a
user-set frequency.

This feature may also be activated via a discrete input terminal (see

Table 6 on

page 138

for further information on this feature).

Settings:

Disabled
On Trip
At Frequency
Trip or At Frequency

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

Power-Line Switching Frequency

Program

Special Control

Power Line Switching Frequency

With the Power Switching parameter enabled, this parameter sets the frequency
at which the At Frequency selection of the Power Switching parameter is
activated.

If the Power Switching function is activated via a discrete input terminal, this
setting sets the frequency at which discrete input terminal is enabled for
activation.

Parameter Type — Numerical

Factory Default — 60.0

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq.

Units — Hz

Power-Line Switching