61

Brake Fault Internal Timer

Program

Protection Settings

Brake Fault Internal Timer

After a brake failure has occurred, the user-set Brake Fault Time clock setting
will begin to count down. Once this time has elapsed, a signal will be provided
to indicate that the brake has failed.

This signal may be used to halt a related system or to notify the user.

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 10.00

Units — Seconds

Break/Make Auto Restart

Program

Protection Settings

Break/Make (Auto Retry)

Enables/Disables the ability of the drive to start into a spinning motor when the
ST-to-CC connection momentarily opens and is then closed (Break/Make ST)
or after a power interruption (momentary power failure).

Settings:

Off
Power Failure
Make/Break ST
Both

Parameter Type — Selection List

Factory Default — Off

Changeable During Run — No

Command Mode

Program

Utilities

Command and Frequency Settings

Command

Mode Select

The Command Mode Selection establishes the source of the command input
for the ASD. Command inputs include Run, Stop, Forward, etc.

Settings:

(Use) (Control Terminal Strip) Terminal Block
(Use) LED Keypad
(Use) Common Serial (TTL)
(Use) RS232/RS485
(Use) Communication Card

Parameter Type — Selection List

Factory Default — Terminal Block

Changeable During Run — No

Commercial (Power) Hold Time

Program

Special Control

Commercial Hold Time

This parameter determines the amount of time that the connection to
commercial power is maintained once the switch-to-drive-output criteria has
been met.

Parameter Type — Selection List

Factory Default — 2.00

Changeable During Run — No

Minimum — 0.10

Maximum — 10.00

Units — Seconds