Bin torque reference reference #1, Bin torque reference reference #2 – Toshiba W7 User Manual

Page 66

Advertising
background image

60

W7 ASD Installation and Operation Manual

BIN Torque Reference Reference #1

Program

Frequency Settings

Speed Reference Setpoints

BIN

BIN Torque Reference Setpoint #1

This parameter is used to set the direction, gain, and bias of the discrete input
terminals when using the discrete input terminals as the control input while
operating in the Torque Control mode.

BIN Input Torque Control Setup

Perform the following setup to allow the system to receive Torque control input
from the discrete input terminals:

Program

Utilities ⇒ Command Mode ⇒ Terminal Block.

Program

Utilities ⇒ Frequency Mode ⇒ Use Binary/BCD Input.

Program

Terminal Settings Input Terminals; select and set the

desired discrete input terminals to Bin Bit(s) 0 – 7 or 0 – MSB (see

Table 6

on page 138

for a listing of the available terminal settings). The binary

terminal input word will control the direction, speed, and torque of the
motor.

Provide a Run command (F or R).

Torque Control

When operating in the Torque Control mode, scaling of the discrete input
terminals is accomplished via the following parameters as described below:

BIN Torque Reference 1,

the binary input value (% of 255

D

) (BIN Speed Ref #1) that represents BIN

Torque Reference 1,

BIN Torque Reference 2, and

the binary input value (% of 255

D

) (BIN Speed Ref #2) that represents BIN

Torque Reference 2.

This is accomplished by establishing an associated V/f output pattern for a given
BIN binary input.

This parameter sets BIN Torque Reference 1 and is the output torque value
that is associated with the setting of BIN Speed Reference 1 when operating in
the Torque control mode.

This value is entered as -250% to 250% of the output torque range.

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — -250.0

Maximum — +250.0

Units — %

Torque Settings

BIN Torque Reference Reference #2

Program

Frequency Settings

Speed Reference Setpoints

BIN

BIN Torque Reference Setpoint #2

This parameter is used to set the direction, gain, and bias of the discrete input
terminals when using the discrete input terminals as the control input while
operating in the Torque Control mode.

This is accomplished by establishing an associated V/f output pattern for a given
BIN binary input.

See

BIN Torque Reference Reference #1

for further information on this

setting.

This parameter sets BIN Torque Reference 2 and is the output torque value
that is associated with the setting of BIN Speed Reference 2 when operating in
the Torque control mode.

This value is entered as -250% to 250% of the output torque range.

Parameter Type — Numerical

Factory Default — +100.0

Changeable During Run — Yes

Minimum — -250.0

Maximum — +250.0

Units — %

BIN Torque Reference Reference #1

BIN Torque Reference Reference #2

Advertising