Cable/Terminal Specifications

Installation should conform to the 2005 National Electrical Code Article 110 (NEC) (Requirements for
Electrical Installations), all regulations of the Occupational Safety and Health Administration, and any
other applicable national, regional, or industry codes and standards.

Note:

The following ratings are guidelines and shall not be the sole determining factor of the
lug or wire size used with the W7 ASD. Application-specific applicables, wire insulation
type, conductor material, and local and regional regulations are but a few of the
considerations when selecting the actual lug and wire type to be used with the W7 ASD.

Note:

Cable/Terminal specifications are based on the rated current of the ASD.

Note:

Use only 75° C copper wire/cable for motor and power connections.

Note:

Input and Output power wires require shielding for CE compliance.

Note:

(*) Indicates that the item is one of a set of two parallel cables.

Note:

(**) Indicates that the item is one of a set of three parallel cables.

Model

MCCB

Rating

(Amps)

Typical Wire/Cable Size (AWG or kcmil)

Lug Size Range

AM, FM, and II

Terminals

Control

Terminals

Input/Output

Power

Wire-Size/

Lug-Capacity

for Input

Power

Wire-Size/

Lug-Capacity

for Output

Power

Recommended

W74600

100

20

(3-core shield)

18

(2-core shield)

3

8 to 3/0

16 to 1

W74750

225

1

3/0 to 350

10 to 1/0

W7410K

225

2/0

12 to 4/0

W7412K

225

3/0

W7415K

400

*1/0

2 to 500

*(6 to 250)

W7420K

400

*3/0

W7425K

600

*250

**(3/0 to 500)

*(1/0 to 500)

W7430K

600

*350

W7440K

800

*500