Pg speed frequency setpoint #1, Pg number of pulses – Toshiba W7 User Manual

Page 103

Advertising
background image

W7 ASD Installation and Operation Manual

97

PG Number of Pulses

Program

Feedback Settings

PG Number of Input Pulses

This parameter is used to set the end-of-travel range when using an encoder on
a motor-driven positioning system (e.g., hoist/crane, etc.).

Parameter Type — Numerical

Factory Default — 500

Changeable During Run — No

Minimum — 1

Maximum — 9999

Units — Pulse Count

PG Speed Frequency Setpoint #1

Program

Frequency Settings

Speed Reference Setpoints

PG

PG Speed Frequency Setpoint #Utilities1

This parameter is used to set the direction, gain, and bias of the PG input when
the PG input is used as the Speed/Direction control input.

The PG input signal is a pulse train originating from a shaft-mounted Encoder.

Note:The PG input terminal is available with the ASD-Multicom

option board only.

PG Input Speed/Direction Control Setup

Perform the following setup to allow the system to receive Speed/Direction
control input at the PG input:

Program

Utilitites ⇒ Command and Frequency Settings ⇒ Frequency

Mode#1 Select

Use Pulse Input.

Program

Utilitites ⇒ Command and Frequency Settings ⇒ Command

Mode Select

⇒ (any setting).

Provide a Run command (F and/or R).

Speed/Direction Control

Perform the following setup to allow the system to perform PG Speed/
Direction
control:

Set PG Speed Frequency #1,

Set the PG input pulse count that represents PG Speed Frequency #1,

Set PG Speed Frequency #2, and

Set the PG input pulse count that represents PG Speed Frequency #2.

Once set, as the PG input pulse count changes, the directional information or
the output frequency of the ASD will vary in accordance with the above
settings.

This parameter sets the PG input pulse count that represents PG Speed
Frequency #1
(direction/speed). The range of values for this parameter is -100
to +100% of the PG input pulse count range.

Note: Further application-specific PG settings may be performed

from the following path: Program

Feedback Settings.

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — -80.0

Maximum — +80.0

Units — Hz

Frequency Settings

PG Number of Pulses

PG Speed Frequency Setpoint #1