W7 ASD Installation and Operation Manual

51

W7 ASD Parameter Descriptions

This section lists the parameters of the W7 ASD alphabetically. The listing includes the access path and
a description of each parameter.

Note: Setup procedures included within this section may require a Reset before performing the

procedure. Application-specific settings may then be performed. The pre-Reset conditions may be
saved (see Type Reset).

4–20 mA Loss Selection

Program

Feedback Settings

4–20 mA Loss Sel

Provides an alternative reference in the event of the loss of the 4–20 mA input
signal.

Settings:

Setting
Max Speed
Min Speed
Hold Last
0 Hz
RS232/RS485 Control
Common Serial Control
Panel Control
Fault
Disable

Parameter Type — Selection List

Factory Default — Disable

Changeable During Run — No

4–20 mA Speed Reference

Program

Feedback Settings

4–20 mA Speed Ref

This setting provides a value to be used in the event that Setting is chosen for
the 4–20 mA Loss selection.

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — No

Minimum — 0.0

Maximum — 80.0

Units — Hz

Abnormal Speed Detection Filter Time

Program

Protection Settings

Abnormal Speed Detection Filter

Time

This parameter sets the time that an overspeed condition must exist to cause a
trip.

Parameter Type — Numerical

Factory Default — 10.0

Changeable During Run — No

Minimum — 0.01

Maximum — 100.00

Units — Seconds

4–20 mA Loss Selection

Abnormal Speed Detection Filter Time