Mode 1/2 switching frequency, Maximum output voltage #2, Maximum output voltage #3 – Toshiba W7 User Manual

Page 90: Maximum output voltage #4, Motor 150% time limit, Maximum output, Voltage #2, Voltage #3, Voltage #4

Advertising
background image

84

W7 ASD Installation and Operation Manual

Maximum Output Voltage #2

Program

Fundamental Parameters

Fundamental #2

Maximum

Output Voltage #2

This parameter sets the maximum value of the output voltage of the ASD for
the #2 Motor Set.

Regardless of the programmed value, the output voltage cannot be higher than
the input voltage.

The actual output voltage will be influenced by the input voltage of the ASD
and the Supply Voltage Compensation parameter setting.

Parameter Type — Numerical

Factory Default — (ASD dependent)

Changeable During Run — Yes

Minimum — 0.0

Maximum — (ASD dependent)

Units — Volts

Maximum Output Voltage #3

Program

Motor Settings

Max Output Voltage #3

This parameter sets the maximum value of the output voltage of the ASD for
the #3 Motor Set.

Regardless of the programmed value, the output voltage cannot be higher than
the input voltage.

The actual output voltage will be influenced by the input voltage of the ASD
and the Supply Voltage Compensation parameter setting.

Parameter Type — Numerical

Factory Default — (ASD dependent)

Changeable During Run — Yes

Minimum — 0.0

Maximum — (ASD dependent)

Units — Volts

Maximum Output Voltage #4

Program

Motor Settings

Max Output Voltage #4

This parameter sets the maximum value of the output voltage of the ASD for
the #4 Motor Set.

Regardless of the programmed value, the output voltage cannot be higher than
the input voltage.

The actual output voltage will be influenced by the input voltage of the ASD
and the Supply Voltage Compensation parameter setting.

Parameter Type — Numerical

Factory Default — (ASD dependent)

Changeable During Run — Yes

Minimum — 0.0

Maximum — (ASD dependent)

Units — Volts

Mode 1/2 Switching Frequency

Program

Frequency Settings

Reference Priority

Mode #1/#2

Switching Frequency

This parameter sets the threshold frequency that will be used in the Reference
Priority Selection
parameter to determine if Frequency Mode #1 or #2 will
control the output of the ASD.

Parameter Type — Numerical

Factory Default — 1.00

Changeable During Run — Yes

Minimum — 0.10

Maximum — Max. Freq.

Units — Hz

Motor 150% Time Limit

Program

Protection Settings

Motor 150% Overload Time Limit

This parameter establishes a time that the motor may operate at 150% of its
rated current before tripping. This setting applies the time/150% reference to
the individual settings of each motor (e.g., this setting references 150% of the
Thermal Protection

setting for the #1 motor).

The unit will trip sooner than the time entered here if the overload is greater
than 150%.

Parameter Type — Numerical

Factory Default — 600

Changeable During Run — Yes

Minimum — 10

Maximum — 2400

Units — Seconds

Maximum Output Voltage #2

Motor 150% Time Limit