Lower limit frequency, Lower deviation limit, Low current trip threshold – Toshiba W7 User Manual

Page 87: Low current trip threshold time, Low output disable boost level

Advertising
background image

W7 ASD Installation and Operation Manual

81

Low Current Trip Threshold

Program

Protection Settings

Low Current Trip Threshold

The Low-current Trip parameter enables this function. The Low Current
Trip Threshold
establishes the low-current threshold value. The threshold
value is entered as a percentage of the maximum rating of the ASD.

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 100.00

Units — A

Low Current Trip Threshold Time

Program

Protection Settings

Low Current Time

When the low-current monitor is enabled, this function sets the time that the
low-current condition must exist to cause a trip.

Parameter Type — Numerical

Factory Default — 0

Changeable During Run — Yes

Minimum — 0

Maximum — 255

Units — Seconds

Lower Deviation Limit

Program

Feedback Settings

Lower Deviation Limit

This parameter determines the maximum amount that the feedback may
decrease the output signal.

Parameter Type — Numerical

Factory Default — 50.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 50.00

Units — %

Lower Limit Frequency

Program

Fundamental Parameters

Fundamental #1

Lower

Limit Frequency

This parameter sets the lowest frequency that the ASD will accept as a
frequency command or frequency setpoint. The ASD will output frequencies
lower than the Lower Limit Frequency when accelerating to the lower limit or
decelerating to a stop. Frequencies below the Lower Limit may also be output
when operating in the PID Control mode, Torque Control mode, or the
Vector Control modes (sensorless or feedback).

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — 0.0

Maximum — Upper Limit

Units — Hz

Low Output Disable Boost Level

Program

PID Setup

Low-output Disable Boost Level

The Low Output Disable feature adds the user-input frequency value to the
commanded frequency (Hz).

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — 0.0

Maximum — Max. Freq.

Units — Hz

Low Current Trip Threshold

Low Output Disable Boost Level

Advertising