116

W7 ASD Installation and Operation Manual

RX Speed Frequency Setpoint #1

Program

Frequency Settings

Speed Reference Setpoints

RX

Speed Frequency Setpoint #1

This parameter is used to set the direction, gain, and bias of the RX input
terminal when the RX terminal is used as the control input while operating in
the Speed Control mode.

RX Input Speed/Direction Control Setup

Perform the following setup to allow the system to receive Speed control input
at the RX input terminal:

• Program

Utilities ⇒ Command and Frequency Settings ⇒ Command

Mode Select

Terminal Block.

• Program

Utilities ⇒ Command and Frequency Settings ⇒ Frequency#1

Mode Select

RX.

• Provide a Run command (F and/or R).

Speed/Direction Control

Perform the following setup to allow the system to perform Speed control from
the RX input terminal:

• Set RX Speed Frequency #1,

• Set the RX input signal level (RX Speed Ref #1) that represents RX Speed

Frequency #1,

• Set

RX Speed Frequency Setpoint #2

, and

• Set the RX input signal level (RX Speed Ref #2) that represents

RX Speed

Frequency Setpoint #2

.

Once set, as the RX input voltage changes, the directional information, and the
output frequency of the ASD will vary in accordance with the above settings.

This parameter sets RX Speed Frequency #1 and is the frequency that is
associated with the setting of

RX Speed Reference Setpoint #1

when

operating in the Speed Control mode.

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — -Max. Freq.

Maximum — +Max. Freq.

Units — Hz

Frequency Settings

RX Speed Frequency Setpoint #2

Program

Frequency Settings

Speed Reference Setpoints

RX

Speed Frequency Setpoint #2

This parameter is used to set the direction, gain, and bias of the RX input
terminal when the RX terminal is used as the control input while operating in
the Speed Control mode.

See

RX Speed Frequency Setpoint #1

for further information on this setting.

This parameter sets

RX Speed Frequency Setpoint #2

and is the frequency

that is associated with the setting of

RX Speed Reference Setpoint #2

when

operating in the Speed Control mode.

Parameter Type — Numerical

Factory Default — 80.0

Changeable During Run — Yes

Minimum — -Max. Freq.

Maximum — +Max. Freq.

Units — Hz

RX Speed Frequency Setpoint #1