VI/II Torque Reference Setpoint #1

Program

Frequency Settings

Speed Reference Setpoints

VI/II

VI/II Torque Reference Setpoint #1

This parameter is used to set the direction, gain, and bias of the VI/II input
terminal when the VI/II terminal is used as the control input while operating in
the Torque Control mode.

VI/II Input Torque Control Setup

Perform the following setup to allow the system to receive Torque control input
at the VI/II input terminal:

• Program

Utilities ⇒ Command and Frequency Settings ⇒ Command

Mode Select

Terminal Block.

• Program

Utilities ⇒ Command and Frequency Settings ⇒ Frequency#1

Mode Select

VI/II.

• Provide a Run command (F and/or R).

Torque Control

Perform the following setup to allow the system to perform Torque control
from the VI/II input terminal:

• Set VI/II Torque Reference #1,

• Set the VI/II input signal level (VI/II Speed Ref #1) that represents the VI/II

Torque Reference #1,

• Set

VI/II Torque Reference Setpoint #2

, and

• Set the VI/II input signal level (VI/II Speed Ref #2) that represents the

VI/II

Torque Reference Setpoint #2

.

This is accomplished by establishing an associated V/f output pattern for a
given VI/II input level.

This parameter sets VI/II Torque Reference #1 and is the output torque value
that is associated with the setting of

VI/II Speed Reference Setpoint #1

when

operating in the Torque control mode.

This value is entered as 0% to 250% of the rated torque.

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.0

Maximum — 250.0

Units — %

Torque Settings

VI/II Torque Reference Setpoint #2

Program

Frequency Settings

Speed Reference Setpoints

VI/II

VI/II Torque Reference Setpoint #2

This parameter is used to set the direction, gain, and bias of the VI/II input
terminal when the VI/II terminal is used as the control input while operating in
the Torque Control mode.

This is accomplished by establishing an associated V/f output pattern for a
given VI/II input level.

See

VI/II Torque Reference Setpoint #1

for further information on this

setting.

This parameter sets

VI/II Torque Reference Setpoint #2

and is the output

torque value that is associated with setting of

VI/II Speed Reference Setpoint

#2

when operating in the Torque control mode.

This value is entered as 0% to 250% of the rated torque.

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.0

Maximum — 250.0

Units — %

VI/II Torque Reference Setpoint #1

VI/II Torque Reference Setpoint #2