148

W7 ASD Installation and Operation Manual

*OLI

ASD Overload

Load requirement in excess of
the capability of the ASD.

• The carrier frequency is too high.

• An excessive load.

• Acceleration time is too short.

• DC damping rate is set too high.

• The motor is starting into a spinning load after a

momentary power failure.

• The ASD is improperly matched to the application.

OLM

Motor Overload

Load requirement in excess of
the capability of the motor.

• V/f parameter improperly set.

• Motor is locked.

• Continuous operation at low speed.

• The load is in excess of what the motor can deliver.

*OLR

Resistor
Overload

Excessive current at the
Dynamic Braking Resistor.

• Deceleration time is too short.

• DBR configuration improperly set.

*OP

Overvoltage

DC bus voltage exceeds
specifications.

• ASD attempting to start into a spinning motor after a

momentary power loss.

• Incoming utility power is above the specified range.

• Decel time is too short.

• Voltage spikes at the 3-phase input; install inductive

filter.

• DBR required.

• DBR resistance value is too high.

• DBR function is turned off.

• Overvoltage Stall feature is turned off.

• System is regenerating.

• Load instability.

• Disable the Ridethrough function (

0302

).

OT

Overtorque

Torque requirement in excess of
the setting of parameter

0616

or

0617

for a time longer than the

setting of parameter

0618

.

• ASD is not correctly matched to the application.

• Parameter

0616

or

0617

setting is too low.

• Obstructed load.

*POFF

Control
Undervoltage

Undervoltage condition at the 5,
15, or the 24 VDC supply.

• Defective Control board.

• Excessive load on power supply.

• Low input voltage.

PtSt

Reference Point

Two speed-reference frequency
setpoint values are too close to
each other.

• Two speed reference frequency setpoints are too close to

each other (increase the difference).

UC

Undercurrent

Output current of the ASD is
below the level defined at
parameter

0611

and remains

there for the time set at
parameter

0612

.

* Reset ignored if active.

EOI

Display

Function

Description

Possible Causes