Rx torque reference setpoint #1, Rx torque reference setpoint #2 – Toshiba W7 User Manual

Page 124

Advertising
background image

118

W7 ASD Installation and Operation Manual

RX Torque Reference Setpoint #1

Program

Frequency Settings

Speed Reference Setpoints

RX

Torque Reference Setpoint #1

This parameter is used to set the direction, gain, and bias of the RX input
terminal when the RX terminal is used as the control input while operating in
the Torque Control mode.

RX Input Torque Control Setup

Perform the following setup to allow the system to receive Torque control input
at the RX input terminal:

• Program

Utilities ⇒ Command and Frequency Settings ⇒ Command

Mode Select

Terminal Block.

• Program

Utilities ⇒ Command and Frequency Settings ⇒ Frequency#1

Mode Select

RX.

• Provide a Run command (F and/or R).

Torque Control

Perform the following setup to allow the system to perform Torque control
from the RX input terminal:

• Set

RX Torque Reference Setpoint #1

,

• Set the RX input signal level (RX Speed Ref #1) that represents the

RX

Torque Reference Setpoint #1

,

• Set

RX Torque Reference Setpoint #2

, and

• Set the RX input signal level (RX Speed Ref #2) that represents the

RX

Torque Reference Setpoint #2

.

This is accomplished by establishing an associated V/f output pattern for a
given RX input level.

This parameter sets RX Torque Reference #1 and is the output torque value
that is associated with the setting of RX Speed Reference #1 when operating in
the Torque control mode.

This value is entered as -250 to +250% of the rated torque.

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — -250.0

Maximum — +250.0

Units — %

Torque Settings

RX Torque Reference Setpoint #2

Program

Frequency Settings

Speed Reference Setpoints

RX

Torque Reference Setpoint #2

This parameter is used to set the direction, gain, and bias of the RX input
terminal when the RX terminal is used as the control input while operating in
the Torque Control mode.

This is accomplished by establishing an associated V/f output pattern for a
given RX input level.

See

RX Torque Reference Setpoint #1

for further information on this setting.

This parameter sets

RX Torque Reference Setpoint #2

and is the output torque

value that is associated with setting of

RX Speed Reference Setpoint #2

when

operating in the Torque control mode.

This value is entered as -250 to +250% of the rated torque.

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — -250.0

Maximum — +250.0

Units — %

RX Torque Reference Setpoint #1

RX Torque Reference Setpoint #2

Advertising