Fl on delay, Fl off delay – Toshiba W7 User Manual

Page 78

Advertising
background image

72

W7 ASD Installation and Operation Manual

Fault Detect Station Number

Program

Communication Settings

Fault Detect Station Number

In a multiple-ASD configuration this setting determines the ASD responsible
for fault notification.

Parameter Type — Selection List

Factory Default — 0

Changeable During Run — Yes

Minimum — 0

Maximum — 64

FL Off Delay

Program

Terminal Settings

Terminal Delays

Output Terminal

Delays

FL

FL Off Delay

This parameter delays the response of the FL output terminals by the
programmed value.

The on and off delay times of the FL terminals may be adjusted to provide
more response time to the device that is connected to the output terminals.

Parameter Type — Numerical

Factory Default — 2.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

FL On Delay

Program

Terminal Settings

Terminal Delays

Output Terminal

Delays

FL

FL On Delay

This parameter delays the response of the FL output terminals by the
programmed value.

The delay may be increased to prevent relay chatter.

Parameter Type — Numerical

Factory Default — 2.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

Fault Detect Station Number

FL On Delay