96

W7 ASD Installation and Operation Manual

Panel Stop Pattern

Program

Panel Control

Panel Stop Pattern

The Decel Stop or Coast Stop settings determine the method used to stop the
motor when using the Stop|Reset key of the keypad.

The Decel Stop setting enables either the Dynamic Braking system or the DC
Injection Braking
system. The Coast Stop setting allows the motor to stop at
the rate allowed by the inertia of the load.

Parameter Type — Selection List

Factory Default — Decel Stop

Changeable During Run — Yes

Panel V/f Group Selection

Program

Panel Control

Panel V/f Group Selection

This parameter is used to select 1 of 4 V/f profiles may be selected and run.
Each V/f profile is comprised of 4 user settings: Base Frequency, Base
Frequency Voltage
, Manual Torque Boost, and Thermal Protection.

Settings:

1
2
3
4

Parameter Type — Selection List

Factory Default — 1

Changeable During Run — Yes

Parity (RS232/RS485/TTL)

Program

Communication Settings

Parity (RS232/RS485/TTL)

This parameter plays a role in the setup of the communications network by
establishing the Parity setting of the communications link.

The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.

Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.

Settings:

No Parity
Even Parity
Odd Parity

Parameter Type — Selection List

Factory Default — Even Parity

Changeable During Run — Yes

PG Disconnect Detection Selection

Program

Feedback Settings

PG Disconnect Detection Selection

This parameter Enables/Disables the system’s monitoring of the PG connection
status when using encoders with line driver outputs.

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — Yes

PG Input Phases

Program

Feedback Settings

PG Input Phases

This setting determines if motor speed and direction will be conveyed by the
encoder.

Settings:

Single-Phase
Two-Phase

Parameter Type — Selection List

Factory Default — Two-Phase

Changeable During Run — No

Panel Stop Pattern

PG Input Phases