106

W7 ASD Installation and Operation Manual

RES Terminal

Program

Terminal Settings

Input Terminals

RES

This parameter selects the functionality of the RES discrete input terminal.

In addition, the input terminal must be specified as Normally Open or
Normally Closed.

This parameter sets the programmable RES terminal to 1 of the 69 possible
functions that are listed in

Table 6 on page 138

.

Parameter Type — Selection List

Factory Default — Reset

Changeable During Run — No

RES Terminal Delay

Program

Terminal Settings

Terminal Delays

Input Terminal

Delays

RES Terminal Delay

This parameter delays the response of the ASD to any change in the RES
terminal input by the programmed value (see waveforms at

F Terminal Delay

).

The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.

Parameter Type — Numerical

Factory Default — 8.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

Ridethrough Mode

Program

Protection Settings

Ridethrough Mode

Enables/Disables the Ridethrough function.

In the event of a momentary power outage or a make/break at ST-to-CC, when
enabled, the Ridethrough function uses regenerative energy to maintain the
control circuitry settings.

Regenerated energy is not used to drive the motor.

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — Yes

Ridethrough Time

Program

Protection Settings

Ridethrough Time

In the event of a momentary power outage, this parameter determines the length
of the Ridethrough time. During a Ridethrough, regenerative energy is used
to maintain the control circuitry settings; it is not used to drive the motor.

The Ridethrough will be maintained for the number of seconds set using this
parameter.

Note: The actual Ridethrough Time is load-dependent.

Parameter Type — Numerical

Factory Default — 2.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 320.0

Units — Seconds

RES Terminal

Ridethrough Time