RX2 Speed Frequency Setpoint #1

Program

Frequency Settings

Speed Reference Setpoints

RX2

RX2 Speed Frequency Setpoint #1

This parameter is used to set the direction, gain, and bias of the RX2 input
terminal when the RX2 terminal is used as the control input while operating in
the Speed Control mode.

Note: The RX2 input terminal is available with the ASD-Multicom

option board only.

RX2 Input Speed/Direction Control Setup

Perform the following setup to allow the system to receive Speed control input
at the RX2 input terminal:

• Program

Utilities ⇒ Command and Frequency Settings ⇒ Command

Mode Select

Terminal Block.

• Program

Utilities ⇒ Command and Frequency Settings ⇒ Frequency#1

Mode Select

RX.

• Provide a Run command (F and/or R).

Speed/Direction Control

Perform the following setup to allow the system to perform Speed control from
the RX2 input terminal:

• Set RX2 Speed Frequency #1,

• Set the RX2 input signal level (RX2 Speed Ref #1) that represents RX2

Speed Frequency #1,

• Set

RX2 Speed Frequency Setpoint #2

, and

• Set the RX2 input signal level (RX2 Speed Ref #2) that represents

RX2

Speed Frequency Setpoint #2

.

Once set, as the RX2 input voltage changes, the directional information, and the
output frequency of the ASD will vary in accordance with the above settings.

This parameter sets RX2 Speed Frequency #1 and is the frequency that is
associated with the setting of RX2 Speed Reference #1 when operating in the
Speed Control mode.

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — -Max. Freq.

Maximum — +Max. Freq.

Units — Hz

Frequency Settings

RX2 Speed Frequency Setpoint #2

Program

Frequency Settings

Speed Reference Setpoints

RX2

RX2 Speed Frequency Setpoint #2

This parameter is used to set the direction, gain, and bias of the RX2 input
terminal when the RX2 terminal is used as the control input while operating in
the Speed Control mode.

See

RX2 Speed Frequency Setpoint #1

for further information on this setting.

This parameter sets RX2 Speed Frequency #2 and is the frequency that is
associated with the setting of RX2 Speed Reference #2 when operating in the
Speed Control mode.

Parameter Type — Numerical

Factory Default — 80.0

Changeable During Run — Yes

Minimum — -Max. Freq.

Maximum — +Max. Freq.

Units — Hz