Terminal on pg. 121, S4 terminal, S5 terminal – Toshiba W7 User Manual

Page 127: S5–s16 terminal delay

Advertising
background image

W7 ASD Installation and Operation Manual

121

S4 Terminal

Program

Terminal Settings

Input Terminals

S4 Terminal

Assignment

This parameter selects the functionality of the S4 discrete input terminal.

In addition, the input terminal must be specified as Normally Open or
Normally Closed.

This parameter sets the programmable S4 terminal to 1 of the 69 possible
functions that are listed in

Table 6 on page 138

.

Parameter Type — Selection List

Factory Default — Emergency Off

Changeable During Run — No

S5 Terminal

Program

Terminal Settings

Input Terminals

S5 Terminal

Assignment

This parameter selects the functionality of the S5 discrete input terminal.

Note: The S5 input terminal may be used without the ASD-

Multicom option board.

Without the ASD-Multicom option board the S5 terminal
settings will be stored in volatile memory. The terminal
setting information will be lost if the system is powered down
or reset.

In addition, the input terminal must be specified as Normally Open or
Normally Closed.

This parameter sets the programmable S5 terminal to 1 of the 69 possible
functions that are listed in

Table 6 on page 138

.

Parameter Type — Selection List

Factory Default — Unassigned

Changeable During Run — No

S5–S16 Terminal Delay

Program

Terminal Settings

Terminal Delays

Input Terminal

Delays

S5–S16 Delays

This parameter delays the response of the ASD to any change in the S5–S16
terminal input by the programmed value (see waveforms at FL Off Delay).

The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.

Note: The S5–S16 input terminals may be used without the ASD-

Multicom option board.

Without the ASD-Multicom option board the S5–S16
terminal settings will be stored in volatile memory. The
terminal setting information will be lost if the system is
powered down or reset.

Parameter Type — Numerical

Factory Default — 8.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

S4 Terminal

S5–S16 Terminal Delay