Commercial (Power) Wait Time

Program

Special Control

Comm Wait Time

This parameter determines the amount of time that the drive will wait before
allowing commercial power to be applied to the motor once the switch-to-
commercial-power criteria has been met.

Parameter Type — Selection List

Factory Default — 0.62

Changeable During Run — No

Minimum — 0.37

Maximum — 10.00

Units — Seconds

Communications Data Type

Program

Communication Settings

Communication Data Type

In the event of a communication error during a transmission, the command that
was transmitted may be cleared or held.

Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.

Settings:

0 — Command Request Cleared
1 — Command Request Held

Parameter Type — Selection List

Factory Default — 0

Changeable During Run — No

Communication Interval (TTL)

Program

Communication Settings

TTL Res Time

This parameter sets the TTL response delay time.

Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 2.00

Units — Seconds

Commercial (Power) Wait Time