W7 ASD Installation and Operation Manual

71

Emergency Off Mode

Program

Protection Settings

Emergency Off Mode Selection

This parameter determines the method used to stop the motor in the event that
an Emergency Off command is received.

This setting may also be associated with the FL terminals to allow the FL relay
to change states when an EOFF condition occurs by setting the FL terminal to
Fault FL (all).

Note: A supplemental emergency stopping system should be used

with the ASD. Emergency stopping should not be a task of
the ASD alone.

Settings:

Deceleration Stop
DC Injection Braking Stop
Coast Stop

Parameter Type — Selection List

Factory Default — Coast Stop

Changeable During Run — No

Emergency Off Mode Time

Program

Protection Settings

Emergency Off Mode Time

When DC Injection is used as a function of receiving an Emergency Off
command, this parameter determines the time that the DC Injection braking is
applied to the motor.

Parameter Type — Numerical

Factory Default — 0.10

Changeable During Run — Yes

Minimum — 0.00

Maximum — 10.00

Units — Seconds

End Frequency

Program

Special Control

End Frequency

This parameter sets the lowest frequency that the ASD will recognize during
deceleration before the ASD goes to 0.0 Hz.

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — 0.0

Maximum — 80.0

Units — Hz

Error Detect Time

Program

Communication Settings

Error Detect Time

This setting determines the length of time that an ASD is monitored for an
error.

Parameter Type — Numerical

Factory Default — 200

Changeable During Run — Yes

Minimum — 0

Maximum — 1000

Units — Seconds

Emergency Off Mode

Error Detect Time