W7 ASD Installation and Operation Manual

Number of Retries

Program

Protection Settings

Number of Retries

After a trip has occurred, this parameter sets the number of times that an
automatic system restart is attempted for a qualified trip.

The trip conditions listed below will not initiate the Retry function:

OCA1, 2, or 3 (Arm Short Ckt),

EPH1 (Input Phase Failure),

EPH0 (Output Phase Failure),

OCL (Startup Overcurrent),

EF1 or 2 (Ground Fault),

EMG (Emergency Off),

EEP1 (EEPROM Fault),

Err2 through Err9 (Main RAM/ROM Fault),

E-10 (Sink/Source Error),

13 (Speed Error), or

17 (Key Error).

See the section titled

General Safety Information on pg. 1

for further

information on this setting.

Parameter Type — Numerical

Factory Default — 0

Changeable During Run — Yes

Minimum — 0

Maximum — 10

ON Terminal

Program

Terminal Settings

Input Terminals

ON

This parameter selects the functionality of the ON discrete input virtual
terminal.

As a virtual terminal, the ON control terminal exists only in memory and is
considered to always be in its True (or connected to CC) state.

It is often practical to assign this terminal to a function that the user desires to
be maintained regardless of external conditions or operations.

This parameter sets the programmable ON terminal to 1 of the 69 possible
functions that are listed in

Table 6 on page 138

.

In addition, the input terminal must be specified as Normally Open or
Normally Closed.

Parameter Type — Selection List

Factory Default — Unassigned

Changeable During Run — No

OUT1 Off Delay

Program

Terminal Settings

Terminal Delays

Output Terminal

Delays

OUT1

OUT1 Off Delay

Once the condition is met to change the state of the OUT1 (A & C) output
contacts, this parameter delays the response of the contacts by the programmed
value (see waveforms at

FL Off Delay

).

The on and off delay times of the OUT1 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.

Parameter Type — Numerical

Factory Default — 2.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

Number of Retries

OUT1 Off Delay