RX2 Torque Reference Setpoint #1

Program

Frequency Settings

Speed Reference Setpoints

RX2

RX2 Torque Reference Setpoint #1

This parameter is used to set the direction, gain, and bias of the RX2 input
terminal when the RX2 terminal is used as the control input while operating in
the Torque Control mode.

RX2 Input Torque Control Setup

Perform the following setup to allow the system to receive Torque control input
at the RX2 input terminal:

• Program

Utilities ⇒ Command and Frequency Settings ⇒ Command

Mode Select

Terminal Block.

• Program

Utilities ⇒ Command and Frequency Settings ⇒ Frequency#1

Mode Select

RX2.

• Provide a Run command (F and/or R).

Torque Control

Perform the following setup to allow the system to perform Torque control
from the RX2 input terminal:

• Set RX2 Torque Reference #1,

• Set the RX2 input signal level (RX2 Speed Ref #1) that represents the RX2

Torque Reference #1,

• Set

RX2 Torque Reference Setpoint #2

, and

• Set the RX2 input signal level (RX2 Speed Ref #2) that represents the

RX2

Torque Reference Setpoint #2

.

This is accomplished by establishing an associated V/f output pattern for a
given RX2 input level.

This parameter sets RX2 Torque Reference #1 and is the output torque value
that is associated with the setting of

RX2 Speed Reference Setpoint #1

when

operating in the Torque control mode.

This value is entered as -250 to +250% of the rated torque.

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — -250.0

Maximum — +250.0

Units — %

Torque Settings

RX2 Torque Reference Setpoint #2

Program

Frequency Settings

Speed Reference Setpoints

RX2

RX2 Torque Reference Setpoint #2

This parameter is used to set the direction, gain, and bias of the RX2 input
terminal when the RX2 terminal is used as the control input while operating in
the Torque Control mode.

This is accomplished by establishing an associated V/f output pattern for a
given RX2 input level.

See

RX2 Torque Reference Setpoint #1

for further information on this setting.

This parameter sets RX2 Torque Reference #2 and is the output torque value
that is associated with setting of

RX2 Speed Reference Setpoint #2

when

operating in the Torque control mode.

This value is entered as -250 to +250% of the rated torque.

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — -250.0

Maximum — +250.0

Units — %

RX2 Torque Reference Setpoint #1

RX2 Torque Reference Setpoint #2