BIN Speed Frequency Setpoint #1

Program

Frequency Settings

Speed Reference Setpoints

BIN

BIN Speed Frequency Setpoint #1

This parameter is used to set the direction, gain, and bias of the discrete input
terminals when using the discrete input terminals as the control input while
operating in the Speed Control mode.

BIN Input Speed/Direction Control Setup

Perform the following setup to allow the system to receive Speed control input
at the discrete input terminals:

Program

Utilities ⇒ Command Mode ⇒ Terminal Block.

Program

Utilities ⇒ Frequency Mode ⇒ Use Binary/BCD Input.

Program

Terminal Settings Input Terminals; select and set the

desired discrete input terminals to Bin Bit(s) 0 – 7 or 0 – MSB (see table

Table 6 on page 138

for a listing of the available terminal settings). The

binary terminal input word will control the direction, speed, and torque of
the motor.

Provide a Run command (F and/or R).

Speed/Direction Control

Perform the following setup to allow the system to perform Speed control from
the BIN input terminals:

Set BIN Speed Frequency #1,

Set the binary input value (% of 255

D

) (BIN Speed Ref #1) that represents

BIN Speed Frequency #1,

Set BIN Speed Frequency #2, and

Set the binary input value (% of 255

D

) (BIN Speed Ref #2) that represents

the BIN Speed Frequency #2.

Note: 255

D

is the decimal equivalent of the 8-bit BIN word with all

input terminals set to one (255 decimal = 11111111 binary).

Once set, as the BIN input word changes, the directional information and the
output frequency of the ASD will vary in accordance with the above settings.

This parameter sets BIN Speed Frequency #1 and is the frequency that is
associated with the setting of BIN Speed Reference 1.

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — -80.0

Maximum — 80.0

Units — Hz

Frequency Settings

BIN Speed Frequency Setpoint #2

Program

Frequency Settings

Speed Reference Setpoints

BIN

BIN Speed Frequency Setpoint #2

This parameter is used to set the direction, gain, and bias of the discrete input
terminals when using the discrete input terminals as the control input while
operating in the Speed Control mode.

See

BIN Speed Frequency Setpoint #1

for further information on this setting.

This parameter sets BIN Speed Frequency #2 and is the frequency that is
associated with the setting of BIN Speed Reference 2.

Parameter Type — Numerical

Factory Default — 80.0

Changeable During Run — Yes

Minimum — -80.0

Maximum — +80.0

Units — Hz

BIN Speed Frequency Setpoint #1

BIN Speed Frequency Setpoint #2