RS232/RS485 Baud Rate

Program

Communication Settings

RS232/RS485 Baud Rate

This parameter sets the RS232/RS485 baud rate.

Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.

Settings:

1200
2400
4800
9600
19200
38400

Parameter Type — Selection List

Factory Default — 9600

Changeable During Run — Yes

RS232/RS485 Communication Time-Out Action

Program

Communication Settings

RS232/RS485 Timeout Action

This parameter plays a role in the setup of the communications network by
determining the action to be taken in the event of a time-out (Time-Out
Action
).

The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.

Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.

Settings:

None
RS232/RS485-Alarm – TTL-None
RS232/RS485-Trip – TTL-None
RS232/RS485-None – TTL-Alarm
RS232/RS485-Alarm – TTL-Alarm
RS232/RS485-Trip – TTL-Alarm
RS232/RS485-None – TTL-Trip
RS232/RS485-Alarm – TTL-Trip
RS232/RS485-Trip – TTL-Trip

Parameter Type — Selection List

Factory Default — 485-Alarm – TTL-
None

Changeable During Run — Yes

RS232/RS485 Communication Time-Out Time

Program

Communication Settings

485 Timeout Time

This parameter plays a role in the setup of the communications network by
setting the time that no activity may exist over the communications link before
the link is severed (Time Out).

The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.

Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.

Parameter Type — Numerical

Factory Default — 0

Changeable During Run — Yes

Minimum — 0

Maximum — 100

Units — Seconds

RS232/RS485 Baud Rate

RS232/RS485 Communication Time-Out Time