Out1 terminal on pg. 89, Out2 terminal on pg. 89, Out1 terminal – Toshiba W7 User Manual

Page 95: Out2 terminal, Out1 on delay, Out2 on delay, Out2 off delay

Advertising
background image

W7 ASD Installation and Operation Manual

89

OUT1 On Delay

Program

Terminal Settings

Terminal Delays

Output Terminal

Delays

OUT1

OUT1 On Delay

Once the condition is met to change the state of the OUT1 (A & C) output
contacts, this parameter delays the response of the contacts by the programmed
value (see waveforms at

FL On Delay

).

The delay may be increased to prevent relay chatter.

Parameter Type — Numerical

Factory Default — 2.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

OUT1 Terminal

Program

Terminal Settings

Output Terminals

OUT1 Terminal

Assignment

This parameter sets the functionality of the OUT1 (A & C) output contacts to 1
of the 58 possible functions that are listed in

Table 7 on page 141

.

The on and off delay times of the OUT1 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.

In addition, the output contacts must be specified as Normally Open or
Normally Closed.

Parameter Type — Selection List

Factory Default — Damper Cmd

Changeable During Run — No

OUT2 Off Delay

Program

Terminal Settings

Terminal Delays

Output Terminal

Delays

OUT2 Off Delay

Once the condition is met to change the state of the OUT2 (A & C) output
contacts, this parameter delays the response of the contacts by the programmed
value (see waveforms at

FL Off Delay

).

The on and off delay times of the OUT2 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.

Parameter Type — Numerical

Factory Default — 2.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

OUT2 On Delay

Program

Terminal Settings

Terminal Delays

Output Terminal

Delays

OUT2 On Delay

This parameter delays the response of the OUT2 (A & C) output contacts by
the programmed value (see waveforms at

FL On Delay

).

The delay may be increased to prevent relay chatter.

Parameter Type — Numerical

Factory Default — 2.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

OUT2 Terminal

Program

Terminal Settings

Output Terminals

OUT2 Terminal

Assignment

This parameter sets the functionality of the OUT2 (A & C) output contacts to 1
of the 58 possible functions that are listed in

Table 7 on page 141

.

The on and off delay times of the OUT2 contacts may be adjusted to provide
more response time to the device that is connected to the output terminals.

In addition, the output contacts must be specified as Normally Open or
Normally Closed.

Parameter Type — Selection List

Factory Default — Acc/Dec Completion

Changeable During Run — No

OUT1 On Delay

OUT2 Terminal