W7 ASD Installation and Operation Manual

S12 Terminal

Program

Terminal Settings

Input Terminals

S12 Terminal

Assignment

This parameter selects the functionality of the S12 discrete input terminal.

Note: The S12 input terminal may be used without the ASD-

Multicom option board.

Without the ASD-Multicom option board the S12 terminal
settings will be stored in volatile memory. The terminal
settings will be lost if the system is powered down or reset.

In addition, the input terminal must be specified as Normally Open or
Normally Closed.

This parameter sets the programmable S12 terminal to 1 of the 69 possible
functions that are listed in

Table 6 on page 138

.

Parameter Type — Selection List

Factory Default — Unassigned

Changeable During Run — No

S1–S4 Terminal Delay

Program

Terminal Settings

Terminal Delays

Input Terminal

Delays

S1–S4 Terminal Delays

This parameter delays the response of the ASD to any change in the S1–S4
terminal input by the programmed value (see waveforms at

FL Off Delay

).

The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.

Parameter Type — Numerical

Factory Default — 8.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

S2 Terminal

Program

Terminal Settings

Input Terminals

S2 Terminal

Assignment

This parameter selects the functionality of the S2 discrete input terminal.

In addition, the input terminal must be specified as Normally Open or
Normally Closed.

This parameter sets the programmable S2 terminal to 1 of the 69 possible
functions that are listed in

Table 6 on page 138

.

Parameter Type — Selection List

Factory Default — Preset Speed Cmd #2

Changeable During Run — No

S3 Terminal

Program

Terminal Settings

Input Terminals

S3 Terminal

Assignment

This parameter selects the functionality of the S3 discrete input terminal.

In addition, the input terminal must be specified as Normally Open or
Normally Closed.

This parameter sets the programmable S3 terminal to 1 of the 69 possible
functions that are listed in

Table 6 on page 138

.

Parameter Type — Selection List

Factory Default — Damper Fdbk

Changeable During Run — No

S12 Terminal

S3 Terminal