Save user parameters, Auto setup for 50 hz, Auto setup for 60 hz – Toshiba W7 User Manual

Page 138: Restore factory defaults, Clear past trips, Clear run timer, New base drive board, Restore user settings, Upgrade firmware, Set eoi memory to default

Advertising
background image

132

W7 ASD Installation and Operation Manual

Type Reset

Program

Utilities

Type Resets

This feature assists the user when performing fault analysis or by allowing a
quick system setup change when required. Performing a Type Reset results in
one of the following user-selected post-reset configurations.

Settings:

Auto Setup for 50 Hz
Auto Setup for 60 Hz
Restore Factory Defaults
Clear Past Trips
Clear Run Timer
New Base Drive Board
Save User Parameters
Restore User Settings
Upgrade Firmware
Set EOI Memory to Default

Parameter Type — Selection List

Factory Default — No Reset

Changeable During Run — No

Undervoltage Detection Time

Program

Protection Settings

Undervoltage Detection Time

This parameter sets the time that the undervoltage condition must exist to cause
an Undervoltage Trip when this function is enabled at the Undervoltage Trip
parameter.

Parameter Type — Numerical

Factory Default — 0.03

Changeable During Run — No

Minimum — 0.00

Maximum — 10.00

Units — Seconds

Undervoltage Stall Level

Program

Protection Settings

Undervoltage Stall Level

This parameter sets the low end of the DC bus voltage threshold that, once it
drops below this setting, will activate the Ridethrough feature. Activation may
be the result of a momentary power loss or an excessive load on the bus
voltage. Once activated, the system will attempt to maintain the bus voltage
level set here until the motor stops.

Note: This feature may decrease deceleration times.

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 50.00

Maximum — 100.0

Units — %

Undervoltage Trip

Program

Protection Settings

Undervolt Trip

This parameter Enables/Disables the Undervoltage Trip function.

When enabled, if the DC bus voltage should exceed the setting of the
Undervoltage Stall level in excess of the duration set at the Undervoltage
Detection Time
,

an Undervoltage Trip is incurred.

A user-selected contact may also be actuated if so configured.

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

Reset

Type Reset

Undervoltage Trip