Vi/ii speed reference setpoint #2, Vi/ii speed frequency setpoint #2, Vi/ii speed reference setpoint #1 – Toshiba W7 User Manual

Page 141: Vi/ii, Speed frequency setpoint #2

Advertising
background image

W7 ASD Installation and Operation Manual

135

VI/II Speed Frequency Setpoint #2

Program

Frequency Settings

Speed Reference Setpoints

VI/II

VI/II Speed Frequency Setpoint #2

This parameter is used to set the gain and bias of the VI/II input terminal when
the VI/II terminal is used as the control input while operating in the Speed
Control
mode.

See

VI/II Speed Frequency Setpoint #1

for further information on this setting.

This parameter sets

VI/II Speed Frequency Setpoint #2

and is the frequency

that is associated with the setting of

VI/II Speed Reference Setpoint #2

when

operating in the Speed Control mode.

Parameter Type — Numerical

Factory Default — 80.0

Changeable During Run — Yes

Minimum — 0.0

Maximum — Max. Freq.

Units — Hz

VI/II Speed Reference Setpoint #1

Program

Frequency Settings

Speed Reference Setpoints

VI/II

VI/II Speed Reference Setpoint #1

This parameter is used to set the gain and bias of the VI/II input terminal when
the VI/II terminal is used as the control input while operating in the Speed
Control
or the Torque Control mode.

See

VI/II Speed Frequency Setpoint #1

for further information on this setting

when used for Speed control.

See

VI/II Torque Reference Setpoint #1

for further information on this setting

when used for Torque control.

This parameter sets the VI/II input level that is associated with

VI/II Speed

Frequency Setpoint #1

when operating in the Speed control mode or is

associated with the

VI/II Torque Reference Setpoint #1

when operating in the

Torque control mode.

This value is entered as 0.0% to 100% of the 0.0 to +10 VDC VI/II input signal
range.

The default value for this parameter is 20%. The II input is commonly used for
the 4 – 20 mA current loop signal where 4 mA equals 20% of a 20 mA signal.
If the VI input is used (0 – 10 VDC input), this parameter may be changed to
0.0% (of the input signal).

Parameter Type — Numerical

Factory Default — 20.00

Changeable During Run — Yes

Minimum — 0.0

Maximum — 100.0

Units — %

VI/II Speed Reference Setpoint #2

Program

Frequency Settings

Speed Reference Setpoints

VI/II

VI/II Speed Reference Setpoint #2

This parameter is used to set the gain and bias of the VI/II input terminal when
the VI/II terminal is used as the control input while operating in the Speed
Control
or the Torque Control mode.

See

VI/II Speed Frequency Setpoint #1

for further information on this setting

when used for Speed control.

See

VI/II Torque Reference Setpoint #1

for further information on this setting

when used for Torque control.

This parameter sets the VI/II input level that is associated with

VI/II Speed

Frequency Setpoint #2

when operating in the Speed control mode or is

associated with the

VI/II Torque Reference Setpoint #2

when operating in the

Torque control mode.

This value is entered as 0.0% to 100% of the 0.0 to +10 VDC VI/II input signal
range.

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.0

Maximum — 100.0

Units — %

VI/II Speed Frequency Setpoint #2

VI/II Speed Reference Setpoint #2