Rr speed frequency setpoint #1 on pg. 107, Rr speed frequency setpoint #1, Rr speed frequency setpoint #2 – Toshiba W7 User Manual

Page 113

Advertising
background image

W7 ASD Installation and Operation Manual

107

RR Speed Frequency Setpoint #1

Program

Frequency Settings

RR

RR Speed Frequency

Setpoint #1

This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Speed
Control
mode.

RR Input Speed Control Setup

Perform the following setup to allow the system to receive Speed control input
at the RR input terminal:

Program

Utilitites ⇒ Command and Frequency Settings ⇒ Frequency

Mode#1 Select

RR.

Program

Utilitites ⇒ Command and Frequency Settings ⇒ Command

Mode Select

⇒ (any setting).

• Provide a Run command (F and/or R).

Speed Control

Perform the following setup to allow the system to perform Speed control from
the RR input terminal:

• Set RR Speed Frequency #1,

• Set the RR input signal level (RR Speed Ref #1) that represents RR Speed

Frequency #1,

• Set RR Speed Frequency #2, and

• Set the RR input signal level (RR Speed Ref #2) that represents RR Speed

Frequency #2.

Once set, as the RR input voltage changes the output frequency of the ASD will
vary in accordance with the above settings.

This parameter sets RR Speed Frequency #1 and is the frequency that is
associated with the setting of RR Speed Reference #1 when operating in the
Speed Control mode.

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — 0.0

Maximum — 80.0

Units — Hz

Frequency Settings

RR Speed Frequency Setpoint #2

Program

Frequency Settings

RR

RR Speed Frequency

Setpoint #2

This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Speed
Control
mode.

See RR Speed Frequency #1 for further information on this setting.

This parameter sets RR Speed Frequency #2 and is the frequency that is
associated with the setting of RR Speed Reference #2 when operating in the
Speed Control mode.

Parameter Type — Numerical

Factory Default — 80.0

Changeable During Run — Yes

Minimum — 0.0

Maximum — 80.0

Units — Hz

RR Speed Frequency Setpoint #1

RR Speed Frequency Setpoint #2

Advertising