56

W7 ASD Installation and Operation Manual

ASD Wait Time

Program

Special Control

Inverter Wait Time

This parameter determines the amount of time that the drive will wait before
outputting a signal to the motor once the switch-to-drive-output criteria has
been met.

Parameter Type — Read-Only

Factory Default — (ASD-dependent)

Changeable During Run — No

ASD Typeform

Program

Utilities

Version

ASD Type

This parameter is read-only and displays the current typeform configuration of
the ASD.

Parameter Type — Read-Only

Factory Default — (ASD-dependent)

Changeable During Run — No

Autotune Control Setting

Program

Motor Settings

Autotune Control Setting

When enabled via the

Autotune Enable

parameter, this parameter sets the

Autotune command status.

Settings:

(Autotune) Disabled
Reset (Motor) Defaults
Enable (Autotune) on Run Command

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

Autotune Enable

Program

Motor Settings

Autotune Enable

This parameter Enables/Disables the Autotune function.

Parameter Type — Selection List

Factory Default — Enabled

Changeable During Run — No

Base Frequency #1

Program

Motor Settings

Base Frequency #1

The Base Frequency setting determines the frequency at which the output
voltage of the ASD reaches its maximum setting. The maximum voltage setting
cannot be more that the input voltage (see the

Maximum Output Voltage #1

parameter). There are four Base Frequency profile settings: #1 – #4.

Note: For proper motor operation, the Base Frequency is

normally set for the name-plated frequency of the motor.

Parameter Type — Numerical

Factory Default — 60.0

Changeable During Run — Yes

Minimum — 25.0

Maximum — 299.0

Units — Hz

ASD Wait Time

Base Frequency #1