W7 ASD Installation and Operation Manual

109

RR Torque Reference Setpoint #1

Program

Frequency Settings

RR

RR Torque Reference

Setpoint #1

This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Torque
Control
mode.

RR Input Torque Control Setup

Perform the following setup to allow the system to receive Torque control input
at the RR input terminal:

• Program

Utilities ⇒ Command and Frequency Settings ⇒ Command

Mode Select

Terminal Block.

• Program

Utilities ⇒ Command and Frequency Settings ⇒ Frequency#1

Mode Select

RR.

• Provide a Run command (F and/or R).

Torque Control

Perform the following setup to allow the system to perform Torque control
from the RR input terminal:

• Set RR Torque Reference #1,

• Set the RR input signal level (RR Speed Ref #1) that represents the RR

Torque Reference #1,

• Set RR Torque Reference #2, and

• Set the RR input signal level (RR Speed Ref #2) that represents the RR

Torque Reference #2.

This is accomplished by establishing an associated V/f output pattern for a
given RR input level.

This parameter sets RR Torque Reference #1 and is the output torque value
that is associated with the setting of RR Speed Reference #1 when operating in
the Torque control mode.

This value is entered as 0.0 to 250% of the output torque range.

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.0

Maximum — 250.0

Units — %

Torque Settings

RR Torque Reference Setpoint #2

Program

Frequency Settings

RR

RR Torque Reference

Setpoint #2

This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Torque
Control
mode.

This is accomplished by establishing an associated V/f output pattern for a
given RR input level.

See RR Torque Reference #1 for further information on this setting.

This parameter sets RR Torque Reference #2 and is the output torque value
that is associated with setting of RR Speed Reference #2 when operating in the
Torque control mode.

This value is entered as 0.0 to 250% of the output torque range.

Parameter Type — Numerical

Factory Default — 100.00

Changeable During Run — Yes

Minimum — 0.0

Maximum — 250.0

Units — %

RR Torque Reference Setpoint #1

RR Torque Reference Setpoint #2