W7 ASD Installation and Operation Manual

Acceleration Time #1

Program

Fundamental Parameters

Fundamental #1

Accel

Time #1

This parameter specifies the programmed time in seconds for the output of the
ASD to go from 0.0 Hz to the Maximum Frequency for the #1 Acceleration
profile. The accel/decel pattern may be set using Accel/Decel #1 Pattern. The
minimum and maximum accel/decel time may be set using S-Pattern Lower
Limit Adjustment
and the S-Pattern Upper Limit Adjustment.

Note: An acceleration time shorter than the load will allow may

cause nuisance tripping and mechanical stress to loads.

Automatic Accel/Decel and Stall settings may lengthen the
acceleration time.

Acceleration

The acceleration rate of a motor is determined by several factors: applied
power, applied load, and the physical properties of the motor (winding
parameters, motor size, etc.). The ASD will control the first of these factors:
input power. The settings of the ASD control the frequency and amplitude of
the applied voltage to the motor.

Under most operating conditions, as the output frequency of the ASD goes up
so does the output voltage (linear acceleration). The ASD has the ability to
modify the relationship between frequency and voltage automatically to
produce smoother operation or increased (starting) torque.

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000

Units — Seconds

Accel #2 Time

Program

Fundamental Parameters

Fundamental #2

Accel

Time #2

This parameter specifies the programmed time in seconds for the output of the
ASD to go from 0.0 Hz to the Maximum Frequency for the #2 Acceleration
profile. The accel/decel pattern may be set using Accel/Decel #2 Pattern. The
minimum and maximum accel/decel time may be set using S-Pattern Lower
Limit Adjustment
and the S-Pattern Upper Limit Adjustment.

This setting is also used to determine the acceleration rate of the Motorized Pot
function.

Note: An acceleration time shorter than the load will allow may

cause nuisance tripping and mechanical stress to loads.

Automatic Accel/Decel and Stall settings may lengthen the
acceleration time.

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000

Units — Seconds